Equipment No. . 

PWP-10/1

Manufacturer . 

Siemens

 

Description . 

10 MW Steam Turbine Set

 

Manufactured .

1978

 

Drawings . 

 
 

Photos . 

 
 

Specifications



    10 MW Steam Turbine Genset, Condensing- / Extraction- type

    Year of manufacture 1978

    Last Revision 1998

    Operating hours total 136 000 Hours

    Shut down 05/2001

    Dismantled and completely refurbished 2004

    Turbine Siemens

    Type EENKS 32/36/80-3

    Nominal Rating 10 000 kW

    Design rating 6 800 kW

    Inlet steam parameters normal . 65 barg, 515 deg C, 53,6 t/h

    Inlet steam parameters max. 80 barg, 520 deg C, 69 t/h

    Extraction 1 20,5 - 24 barg, 15,2 – 25 t/h

    Extraction 2 12,5 - 14 barg, 23,4 - 35 t/h

    Bleeding 0,8 – 1,7 barg, 1,8 – 6 t/h

    Exhaust 0,1 bara, 22 – 26 t/h 46 deg C

    Rotating speed 9 500 / 1 500 rpm

    Condenser

    Steam flow 26 t/h

    Surface 185 m2

    Cooling water temperature inlet 15 deg C

    Cooling water flow 843 m3/h

    Generator Siemens

    Power rating 10 MW

    Apparent power rating 12 500 kVA

    Power factor 0,8

    Voltage 6,3 kV, 50 Hz